VDH/GSMI
Combined Vacuum Substation Circuit Breaker and High-Speed, Mechanically Interlocked Grounding Switch rated 38 kV, 1200 A, 25 / 31.5 / 40 kA
This series is specially designed for application with wind energy collection circuits. It totally replaces traditional use of grounding transformers combined with conventional circuit breakers in every feeder of a wind power substation
|
|
DESIGNATION CODE | |||||
|
|
VDH/GSMI 38.12.25 |
VDH/GSMI 38.12.32 |
VDH/GSMI 38.12.40 |
|||
|
|
Main Breaker | Grounding Switch | Main Breaker | Grounding Switch | Main Breaker | Grounding Switch |
Rated Voltage | kV | 34,5 | 34,5 | 34,5 | |||
Rated Maximum Voltage | kV | 38 | 38 | 38 | |||
Rated Continuous Current | A | 1200 | 1200 | 1200 | |||
Rated Symmetrical Interrupting Capability | kA | 25 | — | 31,5 | — | 40 | — |
Rated Short-Time Current (RMS) | kA (3 seg) | 25 | 12,5 | 31,5 | 12,5 | 40 | 12,5 |
Rated Closing and Latching Current (Peak) | kA | 65 | 33 | 82 | 33 | 104 | 33 |
Dielectric Strength – Power Frecuency | kV | 80 | 80 | 80 | |||
Dielectric Strength – Impulse Full Wave (BIL) | kV | 200 | 200 | 200 | |||
Rated Frecuency | Hz | 50/60 | 50/60 | 50/60 | |||
Rated Closing Time | ms | ≤ 45 | — | ≤ 45 | — | ≤ 45 | — |
Rated Opening Time | ms | ≤ 30 | — | ≤ 30 | — | ≤ 30 | — |
Rated Arcing Time | ms | 4 to 11 | — | 4 to 11 | — | 4 to 11 | — |
Rated Mechanical Switching Time | ms | 12 to 16 | 12 to 16 | 12 to 16 | |||
Maximum Electrical Switching Time | ms | 12 | 12 | 12 |